Meter base guide: socket vs. meter-main

Updated November 20, 2026 · ElectricService101 Editorial Team · 8 min read

Quick answer

For a new house, choose a utility-approved, ringless meter-main combination: 200 amps for most homes, or a Class 320 (400-amp) unit for large all-electric homes. A meter-main puts the meter and the main breaker in one outdoor enclosure, which meets the 2026 NEC requirement for an outdoor service disconnect at one- and two-family dwellings.

What types of meter bases are there?

TypeWhat it includesBest for
Meter socket onlyMeter jaws and service lugsSeparate outdoor disconnect, or utility-only replacements
Meter-main comboMeter socket plus main breakerNew homes under the 2026 NEC
Meter-main with branch spacesMeter, main and a few breaker spacesBarns, shops, EV or A/C circuits at the meter
Meter-main with underground pull sectionWide enclosure with large lugs below the meterHeavy underground laterals
Class 320 meter-main320 A continuous socket, usually two 200 A mains400 A homes

200 amp vs. 400 amp: which meter base do you need?

A 200-amp meter base handles most homes. A 400-amp service uses a Class 320 meter base, rated 320 amps continuous and 400 amps maximum, and usually feeds two 200-amp panels. The decision comes from your electrician's load calculation, which the 2026 NEC moved to Article 120.

What does your utility require?

  • Approved list: buy only a socket your utility lists.
  • Ringless cover: most utilities now require it.
  • EUSERC equipment: many western U.S. utilities require meter bases built to EUSERC (Electric Utility Service Equipment Requirements Committee) standards. These often use a ring-type socket that utilities elsewhere won't accept, so match the standard to your utility.
  • Bypass horns: often required so the meter can be pulled without an outage.
  • Knockouts: sized for the utility's conduit, such as 3-inch for AEP underground.
  • Height: commonly centered 4 to 6 feet above grade.

Why does the 2026 NEC favor meter-mains?

The 2026 NEC deleted Section 230.85 and moved the emergency disconnect rule into 230.70. For one- and two-family dwellings, the service disconnect must now be in a readily accessible outdoor location, on or within sight of the house, and marked EMERGENCY DISCONNECT. An indoor main panel alone no longer qualifies on new services. Details are in our 2026 NEC service changes guide.

How do you land conductors in a meter base?

Strip aluminum conductors cleanly, apply antioxidant compound if the lug manufacturer calls for it, and tighten every lug to the torque value on the label with a calibrated torque tool, as NEC 110.14(D) requires. Loose service lugs are a leading cause of meter base burn-ups.

See the meter bases we recommend in the service parts list.

Frequently asked questions

What is the difference between a meter base and a meter-main?

A meter base (meter socket) only holds the meter and terminates the service conductors. A meter-main combination adds a main breaker in the same enclosure, so it also serves as the service disconnect. Because the 2026 NEC requires an outdoor service disconnect for houses, meter-mains have become the simplest way to comply.

Is a 400 amp meter base really 320 amps?

Yes. Residential 400-amp services use a Class 320 meter base, rated 320 amps continuous and 400 amps maximum. It typically feeds two 200-amp disconnects. Loads above 320 amps continuous need a CT-metered service.

Can I buy any meter base?

No. Most utilities only accept meter sockets from their approved list, and many require ringless covers, bypass horns or a specific knockout size. Check the list before you buy.

How high should a meter base be mounted?

Utilities set the height. AEP, for example, requires the meter centered 4 ft 6 in. to 5 ft 6 in. above final grade, and most utilities use a similar range. The meter must stay accessible for reading and service.

Sources: NFPA 70 (NEC) 2026, 230.70, 225.41, 110.14(D); AEP Customer-Owned Meter Socket Specifications (2025); Skamania PUD, meter bases.