ElectricService101

Wire size · Chart

Service entrance wire size chart

Updated November 20, 2026 · ElectricService101 Editorial Team · 5 min read

Quick answer

For a 120/240-volt single-phase dwelling service, NEC Table 310.12 calls for 4/0 AWG aluminum or 2/0 AWG copper at 200 amps, 2 AWG aluminum or 4 AWG copper at 100 amps, and 600 kcmil aluminum or 400 kcmil copper at 400 amps. The table applies only when the conductors carry the entire load of the dwelling.

NEC Table 310.12 service conductor sizes

Service ratingCopperAluminum
100 A4 AWG2 AWG
125 A2 AWG1/0 AWG
150 A1 AWG2/0 AWG
200 A2/0 AWG4/0 AWG
225 A3/0 AWG250 kcmil
300 A250 kcmil350 kcmil
400 A400 kcmil600 kcmil

Values for 120/240 V, 3-wire, single-phase dwelling services and main feeders. Long runs may need larger conductors for voltage drop.

What cable types are used from the transformer to the meter?

CableWhere it's used
URD (underground residential distribution)Aluminum triplex for service laterals in conduit or direct burial
USE-2Single conductors for underground service entrance
SER / SEUService entrance cable on the building, meter to panel
THHN/THWN-2 in conduitIndividual conductors in a mast or riser

How do you terminate aluminum service conductors?

  1. Strip without nicking the strands.
  2. Wire-brush the strands and apply antioxidant compound if the lug instructions call for it.
  3. Use lugs marked AL/CU.
  4. Torque to the manufacturer's value with a torque wrench or screwdriver (NEC 110.14(D)).

Related: underground service installation and meter base guide.

Frequently asked questions

What size aluminum wire is used for a 200 amp service?

4/0 AWG aluminum for the ungrounded (hot) conductors, per NEC Table 310.12 for single-phase dwelling services. Underground, this is commonly 4/0-4/0-2/0 aluminum URD cable, where the smaller conductor is the neutral.

Can I use copper instead of aluminum for a service?

Yes. A 200-amp service needs 2/0 AWG copper. Copper costs much more per foot, so aluminum is the standard for service laterals and service entrance cable. Both are safe when terminated on lugs rated for the conductor and torqued to specification.

Can the neutral be smaller than the hot conductors?

Often yes. The service neutral is sized for the calculated unbalanced load and grounding requirements, so a reduced neutral such as 2/0 aluminum with 4/0 hots is common on 200-amp services. Your electrician confirms the size.

Sources: NFPA 70 (NEC) Table 310.12, 110.14(D).